Condensing Boiler: What Is a Fully Premixed Condensing Boiler?

Nov 11,2025

Condensing boiler : A fully premixed condensing boiler is a new type of gas-fired boiler that achieves combustion through thorough mixing of gas and air. This approach ensures complete combustion, while the fully premixed condensing boiler also recovers both the sensible and latent heat from the flue gases. By contrast, atmospheric‑pressure cast‑iron boilers employ a partial premix combustion mode and have higher flue gas temperatures than condensing boilers, making them less efficient in terms of energy savings and emission reductions.
Thermal balance of gas-fired steam‑generating boilers. Thermal efficiency is a key performance parameter; the higher it is, the more energy‑efficient the boiler. For small and medium‑sized gas boilers, air preheaters are typically not required, so the enthalpy of the standard cubic meter of gas entering the boiler remains constant. Among the boiler’s heat losses, incomplete combustion of the fuel and heat dissipation account for only a minor share, with flue‑gas heat loss comprising approximately 95%. The lower the exhaust gas temperature, the higher the thermal efficiency.
The main component of natural gas is alkanes, and its combustion products contain a large amount of water vapor, whose latent heat of vaporization accounts for approximately 10% of the heat released during fuel combustion. In conventional atmospheric-pressure boilers, failure to implement condensation‑recovery measures results in a 10% loss of heat. By contrast, condensing boilers remove the water vapor in the flue gases as liquid water, thereby reducing heat losses and improving thermal efficiency.
Exhaust temperature. The flue gas temperature must remain below the flue‑gas dew point to enable the absorption and recovery of the latent heat released during water vapor condensation. For atmospheric‑pressure cast‑iron boilers, the flue‑gas dew point is influenced by the excess‑air ratio; with an excess‑air coefficient between 1.6 and 2.0, the dew point falls below 50°C. In domestic heating systems, radiators are typically used, requiring a return‑water temperature of at least 50°C. Moreover, flue gases contain sulfur oxides and nitrogen oxides, which can cause corrosion of cast‑iron boilers if condensate forms. To prevent such corrosion, the exhaust temperature is generally maintained above 110°C, precluding the recovery of the latent heat from water vapor in the flue gas. Fully premixed condensing boilers employ a fully premixed combustion process, with an excess‑air ratio of approximately 1.2 and a flue‑gas dew point around 55°C. When the return‑water temperature does not exceed 55°C, the water vapor in the flue gas condenses, releasing heat that can be recovered as latent heat. At the same time, the reduced excess air in the flue gas lowers the amount of heat carried away from the furnace, further minimizing heat losses.

TAG: