Energy Tower
1. The nominal cooling conditions of the energy tower: the outdoor wet bulb temperature is 28°C, the water temperature entering and leaving the tower is 37°C and the amount of treated water at 32°C, and other cooling conditions are corrected according to the table below (the water temperature entering and leaving the tower is 37°C) /32°C).
Outdoor wet bulb temperature ( ℃) |
27 |
28 |
29 |
Heat dissipation correction factor |
1.15 |
1.0 |
0.83 |
2. The nominal endothermic condition of the energy tower: the outdoor wet bulb temperature is -2°C, the water temperature of the water entering and leaving the tower is -5°C and -2°C, and the heat absorption of other endothermic conditions is corrected as follows ( The amount of treated water remains unchanged).
Outdoor wet bulb temperature ( ℃ ) |
8 |
6 |
4 |
2 |
0 |
-2 |
Heat absorption correction factor |
1.22 |
1.13 |
1.06 |
1.0 |
0.96 |
0.92 |
Outdoor wet bulb temperature ( ℃ ) |
-4 |
-6 |
-8 |
-10 |
-12 |
-15 |
Heat absorption correction factor |
0.88 |
0.84 |
0.80 |
0.76 |
0.72 |
0.64 |